High-Temperature Resistant (Flame-Retardant) Power Cables-also known as Fluoroplastic High-Temperature Cables or F46 High-Temperature Cables-are suitable for use as power transmission lines for electrical equipment operating within high-temperature ranges and harsh environments, with a rated voltage of 0.6/1 kV or lower.
Implementation Standard: Corporate Standard
Characteristics of High-Temperature Resistant (Flame-Retardant) Power Cables:
1. Rated Voltage U0/U: 0.6/1 kV.
2. Maximum Permissible Operating Temperature of the Cable: 200°C for fluoroplastic insulation and sheathing; 105°C for fluoroplastic insulation with heat-resistant PVC sheathing; 180°C for fluoroplastic insulation with silicone rubber sheathing.
3. During a short circuit (lasting no longer than 5 seconds), the maximum temperature of the cable conductor shall not exceed 250°C.
4. The ambient temperature during cable installation shall not be lower than -15°C.
5. The minimum bending radius during cable installation is specified as follows:
Single-core cables: The bending radius shall be no less than 20 times the cable's outer diameter (20D); Three-core cables: The bending radius shall be no less than 15 times the cable's outer diameter (15D).
6. Power cables featuring fluoroplastic insulation and sheathing exhibit excellent resistance to chemical corrosion, high temperatures, and flame propagation.