Detailed Introduction To Silicone Rubber Insulated (Flame-Retardant) Flexible Power Cables

Apr 20, 2026

Leave a message

Characteristics of Silicone Rubber (Flame-Retardant) Power Cables:

1. Rated Voltage U0/U: 0.6/1 kV
2. Permissible Operating Temperature Range: -60°C to +180°C
3. During a short circuit (lasting no longer than 5 seconds), the maximum temperature of the cable conductors shall not exceed 250°C.
4. The ambient temperature during cable installation shall not be lower than -20°C.
5. The minimum bending radius during cable installation is specified as follows:
Single-core cables: The bending radius shall be no less than 15 times the cable's outer diameter (15D).
Three-core cables: The bending radius shall be no less than 12 times the cable's outer diameter (12D). (D = Cable Outer Diameter)

 

 Silicone Rubber (Flame-Retardant) Power Cable Model Names:

Model | Name
(ZR)-HGG | Silicone Rubber Insulated, Silicone Rubber Sheathed (Flame-Retardant) Flexible Power Cable
(ZR)-HGGP | Silicone Rubber Insulated, Silicone Rubber Sheathed, Copper Wire Braided Shielded (Flame-Retardant) Flexible Power Cable
(ZR)-HGGP2 | Silicone Rubber Insulated, Silicone Rubber Sheathed, Copper Tape Wrapped Shielded (Flame-Retardant) Flexible Power Cable
(ZR)-HGVF | Silicone Rubber Insulated, Nitrile-PVC Sheathed (Flame-Retardant) Flexible Power Cable
(ZR)-HGVFP | Silicone Rubber Insulated, Nitrile-PVC Sheathed, Copper Wire Braided Shielded (Flame-Retardant) Flexible Power Cable
(ZR)-HGVF22 | Silicone Rubber Insulated, Nitrile-PVC Sheathed, Steel Tape Armored (Flame-Retardant) Flexible Power Cable
(ZR)-HGVFP2 | Silicone Rubber Insulated, Nitrile-PVC Sheathed, Copper Tape Wrapped Shielded (Flame-Retardant) Flexible Power Cable


Cable Specifications:

Model | Number of Cores | Nominal Cross-Sectional Area (mm²)
(ZR)-HGG | 1, 2, 3, 4, 5; 3+2, 3+1 | Single-core: 1.5–500; Multi-core: 1.5–240
(ZR)-HGGP | |
(ZR)-HGGP2 | |
(ZR)-HGVF | |
(ZR)-HGVFP | |
(ZR)-HGVF22 | |
(ZR)-HGVFP2 | |


Technical Parameters:

1. DC Resistance of Finished Cable Conductors at 20°C: Must comply with the requirements of the GB/T 3956 standard. When normalized to a cable length of 1 meter, a nominal cross-sectional area of ​​1 mm², and a temperature of 20°C, the DC resistance of copper conductor cores shall not exceed 0.0184 ohms.
2. Insulation Resistance of Finished Cable Insulated Cores: When normalized to a cable length of 1 km and a temperature of 20°C, the insulation resistance of the insulated cores shall be no less than 50 MΩ for conductor cross-sections of 50 mm² and below, and no less than 35 MΩ for cross-sections ranging from 70 mm² to 185 mm².
3. The finished cable shall withstand a power-frequency AC test voltage of 3 kV applied for 5 minutes, without any insulation breakdown.