Mining Electrical Cable

Mining Electrical Cable
Details:
MYIV
Conductor: High purity oxygen free copper
Insulation: XLPE
Sheath: Flame retardant PVC (black)
Voltage Rating: 0.6/1kV to 8.7/10kV
Send Inquiry
Description
Send Inquiry
-

There is gas in coal mines. There is coal dust. These things explode when they meet an electric spark. So the safety standard for cables used underground is much higher than on the surface.

Our cable is a power cable made for fixed installation in coal mines. Its voltage rating goes from 0.6/1kV up to 8.7/10kV. It strictly follows the MT 818 and GB/T 12972 mining cable standards. It also holds the national mining product safety mark certificate, which is the MA mark. You can see the MA mark and number printed on the cable sheath. This can be traced back.

The conductor is high purity oxygen free copper. The structure is Class 2 compact stranded round. Copper conductor has good conductivity and mechanical strength. It is good for fixed installation.

The insulation of the Mining Electrical Cable is XLPE. Compared to mining rubber sheathed cables like MYP, XLPE insulation has a long term working temperature of 90°C. Dielectric loss is very low. It is better for medium voltage 6/10kV long distance power supply. It effectively reduces line voltage drop.

The core is the sheath. We use flame retardant PVC sheath. The color is usually black. This material passes the GB/T 18380.12 single vertical burning test. It self extinguishes when the flame is removed. This means the cable will not start a fire if there is a short circuit underground.

The flame retardant performance meets the MT 386 standard. After burning 6 test samples, the average afterburn time is ≤5 seconds. This is stricter than ordinary flame retardant cables on the surface.

The voltage rating has several levels. 0.6/1kV, 1.8/3kV, 3.6/6kV, 6/10kV, 8.7/10kV. Conductor long term working temperature is 90°C. Short circuit temperature is 250°C. Insulation resistance constant at 20°C is ≥3670 MΩ·km.

It is for fixed installation. Minimum bend radius is 10 times the cable outer diameter for armoured type. Note: It cannot be used on mining faces or mobile equipment. For mobile equipment, choose MYP or MYPTJ rubber sheathed soft cables.

Our factory has been making cables since 2001. That is 25 years now. We have our own R&D team. For OEM/ODM, we can work with your factory if it has the strength and qualifications.

 

Technical Data Table

 

Parameter

Value

Product Name

Mining Electrical Cable

Conductor

High purity oxygen free copper

Insulation

XLPE

Sheath

Flame retardant PVC (black)

Voltage Rating

0.6/1kV to 8.7/10kV

Normal Working Temp

90°C

Short Circuit Temp

250°C

Insulation Resistance

≥3670 MΩ·km (at 20°C)

Flame Retardant

MT 386 (afterburn ≤5 sec)

Min Bend Radius

10 x outer diameter (armoured)

Best Application

Underground mine substations, pump rooms, fixed equipment

Certification

MA mark

Factory Founded

2001

 

Hot Tags: mining electrical cable, China mining electrical cable manufacturers, Dragline Power Cable, mining cables, Mining Power Cable, Underground Mining Cable, Mining Electrical Cable